AVAILABLE CONFIGURATIONS:
with only n° 3 phase clamps |
with only n° 1 earthing rod |
without voltage detector |
with earthing clamp 0÷40 mm |
with phase copper cables sec. 25 or 35 mm2 L=2÷4 m |
with earthing cable L=> 14 m |
n° 4 light alloy clamps with spring tightening ø 3÷20 mm |
n° 1 light alloy clamp holder head, complete of recover hook |
n° 2 copper cables sec. 25 mm2 L=2 m covered with silicone sheath |
n° 1 earthing copper cable sec. 16 mm2 L=14 m covered with silicone sheath |
n° 1 reel for ground cable |
n° 1 voltage detector 4÷30 kV |
n° 2 earthing rods connected by copper cables sec. 16 mm2 L=6 m covered with silicone sheath |
n° 1 insulating stick L=3 m on jointable elements, with nylon bag |
n° 1 metal box |
with only n° 3 phase clamps |
with only n° 1 earthing rod |
without voltage detector |
with earthing clamp 0÷40 mm |
with phase copper cables sec. 25 or 35 mm2 L=2÷4 m |
with earthing cable L=> 14 m |
In accordance to STD IEC 61230 e EN 50110-1
Ref. STF EA 0320-12A ENEL DISTRIB.
Our Mod. BMT 18 EA 0320-12A
Cable sec. mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
25 | 13,7 kA | 8 kA | 5,6 kA |
35 | 15,7 kA | 11,1 kA | 8 kA |